FDA Series

Double Inlet Forward Curved Centrifugal Fans - Forward Wheels

  • The FDA series is DIDW centrifugal fans with forward curved impellers.
  • The fans are suitable for supply or extract applications in commercial, process and industrial HVAC systems.
  • Sizes of the series are in accordance with AMCA standard 99-0098-76 R20.

Dimensions

Type S

This type is supplied with mounting feet and can be mounted in three different orientations.

The construction is mainly for OEM application which only subject to testing and approval.

Fan size: 160 to 710
Volume: 1000 to 50000 m³/h
Total pressure: up to 1400 Pa

Type C

This type has a frame fitted on both sides of the fan which gives better strength and rigidity.

It allows mounting in four different orientations.

Fan size: 160 to 710
Volume: 1000 to 50000 m³/h
Total pressure: up to 1400 Pa

Type T

This type has a welded frame giving increased stiffness and rigidity required for higher operating performance.

Fan size: 250 to 1400
Volume: 2500 to 250 000 m³/h
Total pressure: up to 1600 Pa

Type T

This type has a welded frame giving increased stiffness and rigidity required for higher operating performance.

Fan size: 250 to 1400
Volume: 2500 to 250 000 m³/h
Total pressure: up to 1600 Pa

FDA series are also available in twin fan version with two double inlet fans mounted on the same shaft.  To select for win fans, use the curves of single fan with the following factors: 

  • Volume x 2
  • Absorbed Power x 2.15
  • Speed x 1.05
  • Noise + 3 dB

This series is available in type S2, C2 or T2

Performances of Twin fans are not AMCA licensed

Type C2

 
Size: 250 to 500
Volume:  5000 to 50 000 m3/h

Type S2

 
Size: 250 to 500 
Volume:  5000 to 50 000 m3/h 

Type T2

Size: 355 to 630
Volume:  10 000 to 80 000 m3/h

Fan Rotation and Discharge

The rotation and discharge of the fan is in accordance with AMCA standard 99-2406-83. The direction of rotation is determined from the drive side of the fan:

CW - Clockwise rotation
CCW - Counter -clockwise rotation 

Motor Position 

The position of the motor for belt drive centrifugal fan is in accordance with AMCA standard 99-2407-66.
Location of motor is determined by facing the drive side of fan and designating the positions by letters W, X, Y or Z. 

Motor Selection

The power curve shown on each performance curve represents the absorbed power at the shaft of the fan measured in kW.
To determine the power of the motor to be installed, a correction factors should be applied to compensate for transmission losses.
For conversion to horsepower (HP), use multiplying factor 1.34.

Inspection Doors

The inspection door can be supplied upon request in one of three positions: P3, P4, P5.

Bearings

The bearings are lubricated for life and maintenance-free. If re-lubrication is necessary, it is recommended to use a lithium base grease suitable for all temperatures within the operational limits. Bearings used are either deep groove ball bearing type with an adaptor sleeve or spherical roller bearings type sealed at both sides for different duty appllcation classified as below:

  PDF

       
  Features   Example
Selection
FDA
160 - 280
FDA
315 - 500
FDA
560 - 1000
  Dimensions
Download PDF file   Download PDF file Download PDF file Download PDF file Download PDF file Download pdf file
 

TDE

The Multiflow TDE 500 to 710 range consist of fully cased, cylindrical models with circular mounting flanges at both ends and a wired terminal box.

RVF

The Mini Centrifugal Roof Fan series are the new type roof extract units available in 2 sizes and suitable for vertical and horizontal installation. The low noise external motor and high efficient backward bladed impeller meets the requirement of efficient ventilation in residential, commercial and light industrial applications.

Future 150

The Decor Series can be wall or ceiling mounted and is designed to exhaust stale and moist air from bathrooms, toilets, laundries etc. They are also suitable for ventilating all types of small or closed areas.

TD Silent

The Silent Series is a low profile mixed-flow in-line fan that produces low noise when in operation. It does this through a specifically designed perforated internal skin that directs sound waves produced inside the fan to a layer of sound absorbent material.

NEW!! TD-EVO

The low-profile TD-EVO 250 and 315 in-line mixed-flow fans for circular ducts have a unique design where the support bracket allows the motor and impeller assembly to be fitted or removed without dismantling the adjacent ducting.

History

AMS started trading late in 1994 ...

History

Our Partners

Kruger products are licensed to ...

Our Partners

Company Profile

Air Movement Supplies ...

Profile

Ads

AMS marketing ...

Ads

Certificates

ISO, EC etc ....

Certificates

News

CTN, JHB & DBN news ...

News