Features
|
- The CAB range of acoustically lined cabinet fans, comprising of six nominal sizes, are specifically designed to provide extract ventilation solutions for noise sensitive environments, such as commercial offices, restaurants and cafes, libraries and public buildings etc.
- The models are supplied with a remote mounting wiring outlet box to facilitate installation and connection to external controls.
- Air volume performance ranges from 200 up to 3950 m3/hr.
|
Construction
|
- The fan casings are manufactured from heavy gauge galvanised sheet steel and internally lined with a dense Melinex (M1 type) acoustic insulation of 50mm thickness.
- All models incorporate inlet and discharge circular duct connection flanges with integrated rubber air seal.
- The product is designed for the cover to be removed for access to the motor/impeller without removing the fan casing from the ducting.
- This CAB fan cover is supplied as standard with “quick-fix” fixings to enable fast removal or fitting without tools.
- All models are also supplied with four mounting feet to facilitate any ceiling, wall or floor mounting installation.
|
Motor Impeller
|
- All models incorporate a single phase, 230V 50Hz, direct-drive low pressure forward curved centrifugal fan (with scroll) available in 2 or 4 pole speed.
- The motors are of “enclosed” type and are fully speed controllable using voltage regulation.
|
Dimensions
|
|
|
Model CAB |
A |
B |
C |
DØ |
E |
F |
125 |
273 |
388 |
395 |
125 |
125 |
162 |
160 |
273 |
388 |
395 |
160 |
143 |
162 |
200 |
328 |
430 |
365 |
200 |
216 |
210 |
250 |
383 |
525 |
450 |
250 |
263 |
237 |
315 |
443 |
600 |
505 |
315 |
301 |
264 |
400 |
513 |
660 |
600 |
400 |
331 |
292 |
|
Technical Data
|
|
Nom |
|
Motor |
Max. abs |
Max. air |
Sound pressure level |
|
|
Impeller |
|
power |
current |
volume |
dB(A) @ 1.5m |
|
|
|
Model CAB |
Size |
r.p.m. |
abs. W |
230V |
m3/hr |
Discharge |
Inlet |
Radiated |
Kg |
125 |
140/059 |
1600 |
48 |
0.22 |
240 |
47 |
3 |
30 |
16 |
160 |
140/059 |
2350 |
100 |
0.43 |
390 |
55 |
41 |
36 |
18 |
200 |
133/126 |
2000 |
180 |
0.80 |
695 |
58 |
45 |
34 |
22 |
250 |
180/184 |
1250 |
200 |
0.90 |
1250 |
60 |
44 |
38 |
25 |
250N |
146/180 |
2200 |
350 |
1.5 |
1140 |
62 |
45 |
39 |
27 |
315 |
180/240 |
1400 |
500 |
3.20 |
2100 |
65 |
52 |
40 |
33 |
400 |
240/240 |
1400 |
1100 |
4.80 |
3500 |
69 |
55 |
43 |
35 |
|
Performance
|
Q = Air volume in m3/hr and m3/s |
Pe = Static pressure in mmWG and Pa |
Dry air at 20ºC and 760mmHG |
Air flow data in accordance with the following standards: UNE 100-212-89, Part 1 AMCA 210-85 and ASHRAE 51-1985 |
|
|
|
Sound Data
|
Model CAB |
|
63 |
125 |
250 |
500 |
1000 |
2000 |
4000 |
8000 |
125 |
Discharge |
34.5 |
46.0 |
43.5 |
49.5 |
59.0 |
54.5 |
50.0 |
44.0 |
Inlet |
40.5 |
45.5 |
36.0 |
35.5 |
36.5 |
35.5 |
32.0 |
29.0 |
Radiated |
40.5 |
41.0 |
24.5 |
27.5 |
25.5 |
25.0 |
21.5 |
20.0 |
160 |
Discharge |
38.0 |
55.5 |
55.0 |
60.5 |
65.5 |
65.0 |
60.0 |
56.5 |
Inlet |
42.5 |
53.5 |
44.5 |
43.0 |
40.5 |
44.0 |
43.5 |
40.0 |
Radiated |
39.0 |
50.0 |
37.0 |
35.5 |
33.0 |
31.5 |
30.5 |
31.5 |
200 |
Discharge |
40.0 |
56.0 |
56.5 |
61.5 |
67.5 |
67.5 |
63.0 |
59.5 |
Inlet |
46.0 |
56.0 |
51.0 |
49.5 |
50.0 |
50.5 |
46.0 |
40.0 |
Radiated |
33.0 |
50.0 |
41.5 |
37.0 |
39.5 |
38.0 |
31.5 |
28.5 |
250 |
Discharge |
49.5 |
56.5 |
58.5 |
65.0 |
70.5 |
68.0 |
64.5 |
59.5 |
Inlet |
48.5 |
53.5 |
51.5 |
50.0 |
49.5 |
48.5 |
43.5 |
39.5 |
Radiated |
42.5 |
48.0 |
42.0 |
39.5 |
40.5 |
7.0 |
33.0 |
30.0 |
250N |
Discharge |
48.0 |
57.0 |
58.5 |
65.0 |
70.5 |
72.0 |
68.0 |
64.0 |
Inlet |
50.0 |
54.0 |
51.0 |
49.5 |
47.5 |
52.0 |
48.50 |
42.0 |
Radiated |
40.0 |
46.5 |
43.0 |
42.0 |
44.0 |
45.5 |
40.5 |
33.0 |
315 |
Discharge |
52.5 |
61.5 |
64.0 |
69.0 |
74.0 |
74.5 |
71.5 |
68.0 |
Inlet |
55.0 |
56.5 |
59.5 |
54.5 |
58.5 |
59.5 |
54.0 |
47.0 |
Radiated |
43.0 |
48.0 |
48.5 |
42.0 |
44.5 |
44.5 |
38.5 |
35.5 |
400 |
Discharge |
57.5 |
61.5 |
67.0 |
73.5 |
79.5 |
77.5 |
76.0 |
67.5 |
|
Inlet |
58.5 |
61.0 |
60.0 |
57.0 |
63.5 |
63.5 |
59.0 |
48.0 |
|
Radiated |
39.5 |
50.5 |
51.0 |
49.5 |
51.0 |
46.5 |
40.0 |
33.5 |
|
Autocad
|
|
|
CAB 125 |
CAB 160 |
CAB 200 |
CAB 250 |
|
|
|
|
CAB 315 |
CAB 400 |
|
PDF
|
|
|
|
|
|
|
|
|