Features
|
- The Centrifugal Induction fan, size 100N thrust, is designed to induce air movement in enclosed car parking and for emergency smoke operation at F400 or F300.
|
Construction
|
- The galvanised steel backward curved centrifugal impeller is balanced in accordance with ISO 1940-1, G6.3.
- The fan duct is made from galvanised steel and an inlet steel guard is supplied.
- The external electrical terminal box makes connection easier.
|
Motors Impellers
|
- Motors are totally enclosed airstream cooled, protected to IP55 with each motor matched to the aerodynamic performance of the impeller.
- Motors are Class H insulation for normal continuous duty at maximum ambient 40°C.
- Electricity supply - 400/50 HzV, three-phase.
- Two speed 4/8 pole Dalhander winding.
|
Testing
|
- Complete fan assembly independently tested and approved in accordance with EN12101-3 at F400 or F300.
|
Dimensions
|
|
Technical Data
|
|
Fan |
|
|
Nom |
Max. |
Start |
Sound |
Sound |
|
|
Speed |
Thrust |
Airflow |
Power |
abs |
Current |
level |
Pressure |
|
Model IFHT |
r.p.m. |
N |
m3/hr |
kW |
Cur (A) |
(A) |
(Lwa) |
dB(A)@3m |
Kg |
100N-C-4/8 |
1420/710 |
95/24 |
8900/4450 |
2.3/0.37 |
5.4/109 |
30/7.5 |
95/79 |
78/2 |
120 |
|